This page lists the settings of a Yaskawa controller and of the network before TouchUp connects to it. TouchUp uses the High Speed Ethernet Server (HSES) of the controller. Each setting is made once on the programming pendant, with the security mode set to `MANAGEMENT`.

## Controllers

YRC1000, YRC1000micro, MOTOMAN NEXT, DX200, DX100 and FS100. MotoSim does not answer HSES: a connection needs a real controller.

## Ethernet function

1. Start the controller in maintenance mode.
2. `SYSTEM INFO`, set the security mode to `MANAGEMENT`.
3. `SYSTEM`, `SETUP`, `OPTION FUNCTION`, `NETWORK FUNCTION SETTING`: set `ETHERNET` to `USED`, `ETHERNET SERVER` to `EXPANDED` and `FTP` to `EXPANDED`.
4. In `LAN INTERFACE SETTING`, set the IP address, the subnet mask and the gateway.
5. Restart the controller in normal mode.

If `ETHERNET` stays at `NOT USED` and cannot be changed, the function is not enabled on the controller: ask the Yaskawa support.

## Network

- HSES answers on UDP 10040 (data) and 10041 (files). A firewall between the PC and the controller must let them through.
- The controller must answer a ping from the PC within 200 ms. Turn off the ping before connect only when a firewall blocks ICMP: without it, a wrong address is seen at the first read, after the timeout.

## Parameters

| Use | Parameters |
| --- | --- |
| Connect | `RS000` = 2, `RS005` = 1, `RS007` = 2, `RS022` = 1, `RS029` = 1 |
| Overwrite a file | `RS029` = 1 and `RS214` = 1 |
| Write I/O and variables in play mode | `S2C541` and `S2C542` = 0 on DX200, YRC1000 and YRC1000micro. `S2C409` = 1 on DX100 and FS100 |

## Remote commands

The reads work in any mode. A command (select or start a job) also needs:

- the pseudo input `#82015 CMD REMOTE SEL` enabled, and the key of the pendant in the remote position;
- `JOB SELECT WHEN REMOTE AND PLAY` set to `PERMIT` (`SETUP`, `FUNCTION ENABLE`).

TouchUp shows the missing settings in the result of Test Connection, with the pendant menu to use.

## What to read next

- [Connect to your first controller](/touchup/documentation/first-connection)
- [When the connection fails](/touchup/documentation/connection-failure)